AHI Carrier Catalog | Page 184

Fan with available pressure (option 10) ■■ Selection method The base performances for the calculation are those of option 119 (only MCHE heat exchangers, see pages 24 and 25 of this manual). To obtain the capacities at the static duct pressure, apply the coefficients shown in the tables on the right. Air flow Cooling capacity EER Power input l/s kW kW/kW kW 30XA option 10 Fan pressure drop Air flow Cooling capacity EER Power input Correction factors 0 20 40 0 -3.5 -7.5 0 -0.5 -1.0 0 -1.5 -3.5 0 +1.0 +2.5 Pa % % % % 60 -12.1 -1.5 -5.0 +3.5 Note: All fans must be individually ducted. ■■ Example 30XA 802 with 40 Pa pressure drop Performances option 119 at the following conditions: -- 35 °C outside air temperature -- 12/7 °C entering/leaving water temperature 0 Pa for option 119 Correction factors 40 Pa 54167 787 3.13 251 -7.5% -1.0% -3.5% +2.5% 50119 779 3 258 Application limits for correction factors for high air temperatures 48 60Pa 46 20Pa 44 Outdor air temperature, °C COOLING This option allows a duct connection at the discharge side of the condenser fan. The unit is supplied with axial fans with a speed of 15.8 r/s (same for option 119), each equipped with a duct connection frame. The chiller can operate at a static discharge pressure of up to 60 Pa with reduced performance. The performances can be estimated using the coefficients below, applicable at the conditions shown in the curve below. 42 40 38 36 34 32 30 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Leaving water temperature, °C 184 C A R R I E R 2 0 1 6 / 2 0 1 7