AHI Carrier Catalog | Page 176
Unit with option 119 or with option 119 and option 81
30XA
252
302
352
402
452
504
502
602
702
752
802
854
852
Power circuit
Nominal power supply
V-ph-Hz 400-3-50 ± 10%
Control circuit
24 V via internal transformer
Maximum start-up current*
Circuit 1**
A
274
274
292
407
510
510
510
583
616
782
812
812
815
Circuit 2**
A
-
-
-
-
-
-
-
-
-
-
-
-
-
Option 81
A
-
-
-
-
-
-
-
-
-
-
-
-
-
COOLING
Nominal start-up current***
Circuit 1**
A
246
246
261
379
479
479
479
535
561
734
757
760
760
Circuit 2**
A
-
-
-
-
-
-
-
-
-
-
-
-
-
Option 81
A
-
-
-
-
-
-
-
-
-
-
-
-
-
Cosine Phi (maximum)****
0.88
0.87
0.87
0.88
0.88
0.88
0.88
0.88
0.88
0.86
0.86
0.86
0.86
Cosine Phi (nominal) †
0.84
0.84
0.83
0.83
0.84
0.84
0.84
0.84
0.84
0.83
0.83
0.83
0.83
Maximum power input‡
Circuit 1**
kW
126
136
147
172
192
211
212
257
278
304
323
353
356
Circuit 2**
kW
-
-
-
-
-
-
-
-
-
-
-
-
-
Option 81
kW
-
-
-
-
-
-
-
-
-
-
-
-
-
Nominal unit current draw†
Circuit 1**
A
151
167
182
210
239
267
267
324
349
409
430
446
446
Circuit 2**
A
-
-
-
-
-
-
-
-
-
-
-
-
-
Option 81
A
-
-
-
-
-
-
-
-
-
-
-
-
-
Maximum unit current draw (Un)‡
Circuit 1**
A
208
226
243
284
316
347
350
423
457
512
542
590
596
Circuit 2**
A
-
-
-
-
-
-
-
-
-
-
-
-
-
Option 81
A
Option 231
-
-
-
-
-
-
-
-
-
-
-
-
-
192
207
221
256
285
317
320
383
418
468
499
549
555
Maximum unit current draw (Un – 10%)****
Circuit 1**
A
219
243
262
305
340
373
376
455
491
551
583
634
640
Circuit 2**
A
-
-
-
-
-
-
-
-
-
-
-
-
-
Option 81
A
-
-
-
-
-
-
-
-
-
-
-
-
-
*
Instantaneous start-up current (operating current of the smallest compressor + fan current + locked rotor current in star connection of the largest compressor). Values obtained at
operation with maximum unit power input.
30XA 1402 to 1702 units: circuit 1 supplies circuits A and B, circuit 2 supplies circuits C and D. 30XA 1112, 1212, 1312 and 1382 units: circuit 1 supplies circuit A, circuit 2 supplies
circuit B.
*** Instantaneous start-up current (operating current of the smallest compressor + fan current + locked rotor current in star connection of the largest compressor). Values obtained at
standard Eurovent unit operating conditions: air 35 °C, water 12/7 °C.
**** Values obtained at operation with maximum unit power input.
†
Values obtained at standard Eurovent unit operating conditions: air 35 °C, water 12/7 °C
‡
Values obtained at operation with maximum unit power input. Values given on the unit name plate
Notes:
1. Unit sizes 30XA 1112, 1212, 1312, 1382, 1402 to 1702 have two power connection points.
**
176
C
A
R
R
I
E
R
2
0
1
6
/
2
0
1
7