AHI Carrier Catalog | Page 176

Unit with option 119 or with option 119 and option 81 30XA 252 302 352 402 452 504 502 602 702 752 802 854 852 Power circuit Nominal power supply V-ph-Hz 400-3-50 ± 10% Control circuit 24 V via internal transformer Maximum start-up current* Circuit 1** A 274 274 292 407 510 510 510 583 616 782 812 812 815 Circuit 2** A - - - - - - - - - - - - - Option 81 A - - - - - - - - - - - - - COOLING Nominal start-up current*** Circuit 1** A 246 246 261 379 479 479 479 535 561 734 757 760 760 Circuit 2** A - - - - - - - - - - - - - Option 81 A - - - - - - - - - - - - - Cosine Phi (maximum)**** 0.88 0.87 0.87 0.88 0.88 0.88 0.88 0.88 0.88 0.86 0.86 0.86 0.86 Cosine Phi (nominal) † 0.84 0.84 0.83 0.83 0.84 0.84 0.84 0.84 0.84 0.83 0.83 0.83 0.83 Maximum power input‡ Circuit 1** kW 126 136 147 172 192 211 212 257 278 304 323 353 356 Circuit 2** kW - - - - - - - - - - - - - Option 81 kW - - - - - - - - - - - - - Nominal unit current draw† Circuit 1** A 151 167 182 210 239 267 267 324 349 409 430 446 446 Circuit 2** A - - - - - - - - - - - - - Option 81 A - - - - - - - - - - - - - Maximum unit current draw (Un)‡ Circuit 1** A 208 226 243 284 316 347 350 423 457 512 542 590 596 Circuit 2** A - - - - - - - - - - - - - Option 81 A Option 231 - - - - - - - - - - - - - 192 207 221 256 285 317 320 383 418 468 499 549 555 Maximum unit current draw (Un – 10%)**** Circuit 1** A 219 243 262 305 340 373 376 455 491 551 583 634 640 Circuit 2** A - - - - - - - - - - - - - Option 81 A - - - - - - - - - - - - - * Instantaneous start-up current (operating current of the smallest compressor + fan current + locked rotor current in star connection of the largest compressor). Values obtained at operation with maximum unit power input. 30XA 1402 to 1702 units: circuit 1 supplies circuits A and B, circuit 2 supplies circuits C and D. 30XA 1112, 1212, 1312 and 1382 units: circuit 1 supplies circuit A, circuit 2 supplies circuit B. *** Instantaneous start-up current (operating current of the smallest compressor + fan current + locked rotor current in star connection of the largest compressor). Values obtained at standard Eurovent unit operating conditions: air 35 °C, water 12/7 °C. **** Values obtained at operation with maximum unit power input. † Values obtained at standard Eurovent unit operating conditions: air 35 °C, water 12/7 °C ‡ Values obtained at operation with maximum unit power input. Values given on the unit name plate Notes: 1. Unit sizes 30XA 1112, 1212, 1312, 1382, 1402 to 1702 have two power connection points. ** 176 C A R R I E R 2 0 1 6 / 2 0 1 7