AHI Carrier Catalog | Page 174

Physical data, sizes 904 to 1702 30XA 904 902 1002 1112 1212 1312 1382 1402 1502 1702 Cooling Operating weight** Standard unit + option 119* kg 6920 7258 7836 8210 8590 9310 9390 3953/ 7776 3953/ 7926 6958/ 6958 Standard unit + option 254/255* kg - 8620 8870 8920 9330 10050 10140 4460/ 8830 4460/ 8950 7880/ 7880 COOLING Compressors 06T semi-hermetic screw compressors, 50 r/s Circuit A + B 1+1 1+1 1+1 1+1 1+1 1+1 1+1 1+1 1+1 1+1 Circuit C + D - - - - - - - 1+0 1+0 1+1 Refrigerant** -Standard unit + option 119* R-134a Circuit A + B kg 67/67 69/76 75/79 80/116 80/124 110/116 116/124 84/78 85/88 72/63 Circuit C+ D kg - - - - - - - 80/- 80/- 72/63 Standard unit + options 254/255* Circuit A + B kg - 129+103 140/129 - - - - 140/103 140/129 130/95 Circuit C+ D kg - - - - - - - 135/- 135/- 130/95 % 15 8 10 10 8 Capacity control Minimum capacity Touch Pilot, electronic expansion valve (EXV), minimum capacity 15% 15 15 8 Condensers All-aluminium micro-channel heat exchanger Fans Axial Flying Bird 4, rotating shroud 8 8 Standard unit + option 119* 12 14 16 19 20 20 20 24 24 28 Total air flow Quantity l/s 54167 63194 72222 85764 90278 90278 90278 108333 108333 126389 Rotation speed r/s 15.7 15.7 15.7 15.7 15.7 15.7 15.7 15.7 15.7 15.7 Fans - Standard unit + options 254/255* Quantity Total air flow l/s Rotation speed r/s Evaporator Water content - 15 16 19 20 20 20 24 24 28 - 47833 54667 64917 68333 68333 68333 82000 82000 95667 - 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 11.7 164 174 180 180 230 240 240 Flooded shell-and-tube type l Without hydronic module 130 130 140 Max. water-side pressure 1000 kPa, Victaulic water inlet and outlet connections Nominal diameter‡ in 6 6 8 6 6 6 6 08-juin 08-juin 6 Actual outside diameter‡ mm 168.3 168.3 219.1 168.3 168.3 168.3 168.3 219.1/ 168.3 219.1/ 168.3 168.3 Chassis paint colour Colour Colour code: RAL7035 † Eurovent-certified performances in accordance with standard EN14511-3:2013. Cooling mode conditions: evaporator water entering/leaving temperature 12°C/7°C, outside air temperature 35°C. evaporator fouling factor 0 m2 K/W †† Gross performances, not in accordance with EN14511-3:2013. These performances do not take into account the correction for the proportional heating capacity and power input generated by the water pump to overcome the internal pressure drop in the heat exchanger. Evaporator water entering/leaving temperature 12°C/7°C, outside air temperature 35°C. evaporator fouling factor 0 m2 K/W * Options: 119 = High energy efficiency, 257 = low noise level, 279 = compressor enclosure, 258,= very low sound level, 254 = traditional coils (Cu/Al), 255 = traditional coils (Cu/Al) without slots ** Weights are guidelines only. Refer to the unit nameplate. *** in dB ref=10-12 W, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). Measured in accordance with ISO 9614-1 and certified by Eurovent. **** in dB ref 20µPa, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). For information, calculated from the sound power level Lw(A). ‡ Evporator 1 and 2 connection diameters for sizes 1402 to 1502. Eurovent certified data Notes: 1 Unit sizes 30XA 1402 to 1702 are supplied in two field-assembled modules. 2 Option 119 can be used with options 254 or 255. Contact your Carrier representative for the performances. 174 C A R R I E R 2 0 1 6 / 2 0 1 7