Physical data, sizes 904 to 1702
30XA
904
902
1002
1112
1212
1312
1382
1402
1502
1702
Cooling
Operating weight**
Standard unit + option 119*
kg
6920
7258
7836
8210
8590
9310
9390
3953/
7776
3953/
7926
6958/
6958
Standard unit + option 254/255*
kg
-
8620
8870
8920
9330
10050
10140
4460/
8830
4460/
8950
7880/
7880
COOLING
Compressors
06T semi-hermetic screw compressors, 50 r/s
Circuit A + B
1+1
1+1
1+1
1+1
1+1
1+1
1+1
1+1
1+1
1+1
Circuit C + D
-
-
-
-
-
-
-
1+0
1+0
1+1
Refrigerant** -Standard unit + option 119* R-134a
Circuit A + B
kg
67/67
69/76
75/79
80/116
80/124
110/116
116/124
84/78
85/88
72/63
Circuit C+ D
kg
-
-
-
-
-
-
-
80/-
80/-
72/63
Standard unit + options 254/255*
Circuit A + B
kg
-
129+103
140/129
-
-
-
-
140/103
140/129
130/95
Circuit C+ D
kg
-
-
-
-
-
-
-
135/-
135/-
130/95
%
15
8
10
10
8
Capacity control
Minimum capacity
Touch Pilot, electronic expansion valve (EXV), minimum capacity 15%
15
15
8
Condensers
All-aluminium micro-channel heat exchanger
Fans
Axial Flying Bird 4, rotating shroud
8
8
Standard unit + option 119*
12
14
16
19
20
20
20
24
24
28
Total air flow
Quantity
l/s
54167
63194
72222
85764
90278
90278
90278
108333
108333
126389
Rotation speed
r/s
15.7
15.7
15.7
15.7
15.7
15.7
15.7
15.7
15.7
15.7
Fans - Standard unit + options 254/255*
Quantity
Total air flow
l/s
Rotation speed
r/s
Evaporator
Water content
-
15
16
19
20
20
20
24
24
28
-
47833
54667
64917
68333
68333
68333
82000
82000
95667
-
11.7
11.7
11.7
11.7
11.7
11.7
11.7
11.7
11.7
164
174
180
180
230
240
240
Flooded shell-and-tube type
l
Without hydronic module
130
130
140
Max. water-side pressure 1000 kPa, Victaulic water inlet and outlet connections
Nominal diameter‡
in
6
6
8
6
6
6
6
08-juin
08-juin
6
Actual outside diameter‡
mm
168.3
168.3
219.1
168.3
168.3
168.3
168.3
219.1/
168.3
219.1/
168.3
168.3
Chassis paint colour Colour
Colour code: RAL7035
† Eurovent-certified performances in accordance with standard EN14511-3:2013.
Cooling mode conditions: evaporator water entering/leaving temperature 12°C/7°C, outside air temperature 35°C. evaporator fouling factor 0 m2 K/W
†† Gross performances, not in accordance with EN14511-3:2013. These performances do not take into account the correction for the proportional heating capacity and power input
generated by the water pump to overcome the internal pressure drop in the heat exchanger. Evaporator water entering/leaving temperature 12°C/7°C, outside air temperature 35°C.
evaporator fouling factor 0 m2 K/W
*
Options: 119 = High energy efficiency, 257 = low noise level, 279 = compressor enclosure, 258,= very low sound level, 254 = traditional coils (Cu/Al), 255 = traditional coils (Cu/Al)
without slots
** Weights are guidelines only. Refer to the unit nameplate.
*** in dB ref=10-12 W, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). Measured in accordance with
ISO 9614-1 and certified by Eurovent.
**** in dB ref 20µPa, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). For information, calculated from
the sound power level Lw(A).
‡
Evporator 1 and 2 connection diameters for sizes 1402 to 1502.
Eurovent certified data
Notes:
1
Unit sizes 30XA 1402 to 1702 are supplied in two field-assembled modules.
2
Option 119 can be used with options 254 or 255. Contact your Carrier representative for the performances.
174