AHI Carrier Catalog | Page 171

AIR-COOLED LIQUID CHILLERS 30XA 252-1702 Physical data, sizes 252 to 852 30XA 252 302 352 402 452 504 502 602 702 752 802 854 852 Cooling kW 267 291 318 378 426 - 473 601 654 691 759 - 807 ESEER kW/kW 3.94 4.20 4.20 4.10 4.13 - 4.09 4.08 4.10 4.00 4.06 - 4.09 EER kW/kW 3.00 2.96 2.98 3.08 2.89 - 2.93 3.03 3.11 2.91 2.88 - 2.98 B B B C - B B A B C - B Eurovent class cooling B Air conditioning application††- standard unit Nominal cooling capacity kW 267 291 319 379 427 - 475 603 656 693 761 - 809 ESEER kW/kW 4.03 4.30 4.31 4.26 4.30 - 4.25 4.25 4.25 4.14 4.19 - 4.25 EER kW/kW 3.02 2.98 3.01 3.12 2.92 - 2.97 3.07 3.15 2.94 2.91 - 3.01 Air conditioning application as per EN14511-3:2013† - unit with option 119 Nominal cooling capacity kW 273 298 325 391 442 498 499 612 679 723 785 824 841 ESEER kW/kW 3.89 3.96 4.01 3.88 3.93 3.74 3.93 3.84 4.07 3.87 3.92 3.76 4.03 EER kW/kW 3.13 3.10 3.09 3.21 3.08 3.07 3.15 3.13 3.31 3.08 3.10 3.10 3.24 A B A B B A A A B A A A Eurovent class cooling A COOLING Air conditioning application as per EN14511-3:2013† - standard unit and unit with option 279* Nominal cooling capacity Nominal cooling capacity kW 273 298 325 392 443 499 500 614 681 726 787 826 844 ESEER kW/kW 3.97 4.04 4.10 4.03 4.08 3.85 4.08 4.00 4.22 4.01 4.05 3.88 4.18 EER kW/kW 3.15 3.12 3.12 3.25 3.12 3.11 3.19 3.18 3.35 3.12 3.13 3.14 3.28 IPLV - standard unit kW/kW 4.41 4.50 4.77 4.73 4.75 - 4.77 4.54 4.67 4.58 4.55 - 4.66 IPLV - unit with option 119* kW/kW 4.31 4.37 4.56 4.38 4.51 4.33 4.51 4.35 4.64 4.40 4.47 4.41 4.55 Sound levels - Standard unit Sound power level*** dB(A) 99 99 99 98 101 - 98 100 98 103 102 - 100 Sound pressure level at 10 m**** dB(A) 67 67 67 65 69 - 65 67 65 70 70 - 67 Standard unit + option 279* Sound power level*** dB(A) 89 89 89 92 93 - 93 95 94 96 96 - 95 Sound pressure level at 10 m**** dB(A) 57 57 57 60 61 - 61 62 61 63 64 - 63 Standard unit + option 257* Sound power level*** dB(A) 87 87 87 90 91 - 91 93 92 94 94 - 94 Sound pressure level at 10 m**** dB(A) 55 55 55 58 59 - 59 60 59 61 61 - 61 Standard unit + option 258* Sound power level*** dB(A) - - - - 89 - 89 91 90 91 92 - 91 Sound pressure level at 10 m**** dB(A) - - - - 57 - 56 58 57 59 59 - 59 Sound power level*** dB(A) 100 100 100 100 102 100 100 102 100 104 104 102 102 Sound pressure level at 10 m**** dB(A) 68 68 68 68 70 68 68 69 68 71 71 70 69 HEATING HEATING Air conditioning application††- standard unit + option 119* Sound power level*** dB(A) 94 94 95 96 96 96 96 98 97 98 99 98 98 Sound pressure level at 10 m**** dB(A) 62 62 63 64 64 64 64 66 64 65 66 65 65 Dimensions - standard unit Length mm 3604 3604 3604 4798 4798 4798 5992 7186 7186 7186 7186 7186 8380 Width mm 2253 2253 2253 2253 2253 2253 2253 2253 2253 2253 2253 2253 2253 Height mm 2297 2297 2297 2297 2297 2297 2297 2297 2297 2297 2297 2297 2297 Dimensions - standard unit + options 254/255* Length mm 3604 3604 4798 4798 4798 - 5992 7186 7186 8380 8380 - 8380 Width mm 2253 2253 2253 2253 2253 - 2253 2253 2253 2253 2253 - 2253 Height mm 2297 2297 2297 2297 2297 - 2297 2297 2297 2297 2297 - 2297 † Eurovent-certified performances in accordance with standard EN14511-3:2013. Cooling mode conditions: evaporator water entering/leaving temperature 12°C/7°C, outside air temperature 35°C. evaporator fouling factor 0 m2 K/W †† Gross performances, not in accordance with EN14511-3:2013. These performances do not take into account the correction for the proportional heating capacity and power input generated by the water pump to overcome the internal pressure drop in the heat exchanger. Evaporator water entering/leaving temperature 12°C/7°C, outside air temperature 35°C. evaporator fouling factor 0 m2 K/W * Options: 119 = High energy efficiency, 257 = low noise level, 279 = compressor enclosure, 258,= very low sound level, 254 = traditional coils (Cu/Al), 255 = traditional coils (Cu/Al) without slots ** Weights are guidelines only. Refer to the unit nameplate. *** in dB ref=10-12 W, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). Measured in accordance with ISO 9614-1 and certified by Eurovent. **** in dB ref 20µPa, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). For information, calculated from the sound power level Lw(A). ‡ Evporator 1 and 2 connection diameters for sizes 1402 to 1502. Eurovent certified data Notes: 1 Unit sizes 30XA 1402 to 1702 are supplied in two field-assembled modules. 2 Option 119 can be used with options 254 or 255. Contact your Carrier representative for the performances. C A R R I E R 2 0 1 6 / 2 0 1 7 171 CONTROLS Standard unit + option 119* + 279* AIR TREATMENT Standard unit + option 119*