AIR-COOLED LIQUID CHILLERS 30XA 252-1702
Physical data, sizes 252 to 852
30XA
252
302
352
402
452
504
502
602
702
752
802
854
852
Cooling
kW
267
291
318
378
426
-
473
601
654
691
759
-
807
ESEER
kW/kW 3.94
4.20
4.20
4.10
4.13
-
4.09
4.08
4.10
4.00
4.06
-
4.09
EER
kW/kW 3.00
2.96
2.98
3.08
2.89
-
2.93
3.03
3.11
2.91
2.88
-
2.98
B
B
B
C
-
B
B
A
B
C
-
B
Eurovent class cooling
B
Air conditioning application††- standard unit
Nominal cooling capacity
kW
267
291
319
379
427
-
475
603
656
693
761
-
809
ESEER
kW/kW 4.03
4.30
4.31
4.26
4.30
-
4.25
4.25
4.25
4.14
4.19
-
4.25
EER
kW/kW 3.02
2.98
3.01
3.12
2.92
-
2.97
3.07
3.15
2.94
2.91
-
3.01
Air conditioning application as per EN14511-3:2013† - unit with option 119
Nominal cooling capacity
kW
273
298
325
391
442
498
499
612
679
723
785
824
841
ESEER
kW/kW 3.89
3.96
4.01
3.88
3.93
3.74
3.93
3.84
4.07
3.87
3.92
3.76
4.03
EER
kW/kW 3.13
3.10
3.09
3.21
3.08
3.07
3.15
3.13
3.31
3.08
3.10
3.10
3.24
A
B
A
B
B
A
A
A
B
A
A
A
Eurovent class cooling
A
COOLING
Air conditioning application as per EN14511-3:2013† - standard unit and unit with option 279*
Nominal cooling capacity
Nominal cooling capacity
kW
273
298
325
392
443
499
500
614
681
726
787
826
844
ESEER
kW/kW 3.97
4.04
4.10
4.03
4.08
3.85
4.08
4.00
4.22
4.01
4.05
3.88
4.18
EER
kW/kW 3.15
3.12
3.12
3.25
3.12
3.11
3.19
3.18
3.35
3.12
3.13
3.14
3.28
IPLV - standard unit
kW/kW 4.41
4.50
4.77
4.73
4.75
-
4.77
4.54
4.67
4.58
4.55
-
4.66
IPLV - unit with option 119*
kW/kW 4.31
4.37
4.56
4.38
4.51
4.33
4.51
4.35
4.64
4.40
4.47
4.41
4.55
Sound levels - Standard unit
Sound power level***
dB(A)
99
99
99
98
101
-
98
100
98
103
102
-
100
Sound pressure level at 10 m****
dB(A)
67
67
67
65
69
-
65
67
65
70
70
-
67
Standard unit + option 279*
Sound power level***
dB(A)
89
89
89
92
93
-
93
95
94
96
96
-
95
Sound pressure level at 10 m****
dB(A)
57
57
57
60
61
-
61
62
61
63
64
-
63
Standard unit + option 257*
Sound power level***
dB(A)
87
87
87
90
91
-
91
93
92
94
94
-
94
Sound pressure level at 10 m****
dB(A)
55
55
55
58
59
-
59
60
59
61
61
-
61
Standard unit + option 258*
Sound power level***
dB(A)
-
-
-
-
89
-
89
91
90
91
92
-
91
Sound pressure level at 10 m****
dB(A)
-
-
-
-
57
-
56
58
57
59
59
-
59
Sound power level***
dB(A)
100
100
100
100
102
100
100
102
100
104
104
102
102
Sound pressure level at 10 m****
dB(A)
68
68
68
68
70
68
68
69
68
71
71
70
69
HEATING HEATING
Air conditioning application††- standard unit + option 119*
Sound power level***
dB(A)
94
94
95
96
96
96
96
98
97
98
99
98
98
Sound pressure level at 10 m****
dB(A)
62
62
63
64
64
64
64
66
64
65
66
65
65
Dimensions - standard unit
Length
mm
3604
3604
3604
4798
4798
4798
5992
7186
7186
7186
7186
7186
8380
Width
mm
2253
2253
2253
2253
2253
2253
2253
2253
2253
2253
2253
2253
2253
Height
mm
2297
2297
2297
2297
2297
2297
2297
2297
2297
2297
2297
2297
2297
Dimensions - standard unit + options 254/255*
Length
mm
3604
3604
4798
4798
4798
-
5992
7186
7186
8380
8380
-
8380
Width
mm
2253
2253
2253
2253
2253
-
2253
2253
2253
2253
2253
-
2253
Height
mm
2297
2297
2297
2297
2297
-
2297
2297
2297
2297
2297
-
2297
† Eurovent-certified performances in accordance with standard EN14511-3:2013.
Cooling mode conditions: evaporator water entering/leaving temperature 12°C/7°C, outside air temperature 35°C. evaporator fouling factor 0 m2 K/W
†† Gross performances, not in accordance with EN14511-3:2013. These performances do not take into account the correction for the proportional heating capacity and power input
generated by the water pump to overcome the internal pressure drop in the heat exchanger. Evaporator water entering/leaving temperature 12°C/7°C, outside air temperature 35°C.
evaporator fouling factor 0 m2 K/W
*
Options: 119 = High energy efficiency, 257 = low noise level, 279 = compressor enclosure, 258,= very low sound level, 254 = traditional coils (Cu/Al), 255 = traditional coils (Cu/Al)
without slots
** Weights are guidelines only. Refer to the unit nameplate.
*** in dB ref=10-12 W, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). Measured in accordance with
ISO 9614-1 and certified by Eurovent.
**** in dB ref 20µPa, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)). For information, calculated from
the sound power level Lw(A).
‡
Evporator 1 and 2 connection diameters for sizes 1402 to 1502.
Eurovent certified data
Notes:
1
Unit sizes 30XA 1402 to 1702 are supplied in two field-assembled modules.
2
Option 119 can be used with options 254 or 255. Contact your Carrier representative for the performances.
C
A
R
R
I
E
R
2
0
1
6
/
2
0
1
7
171
CONTROLS
Standard unit + option 119* + 279*
AIR TREATMENT
Standard unit + option 119*