AIR-COOLED LIQUID CHILLERS WITH
INTEGRATED HYDRONIC MODULE 30RB 602-802
Physical data
30RB units
602
672
732
802
Cooling
Full load performances*
C1
Nominal capacity
kW
606.9
657.3
711.8
774.4
C1
EER
kW/kW
2.72
2.68
2.59
2.58
C1
Eurovent Energy Class
C
D
D
D
kW/kW
3.97
3.88
3.75
3.71
Sound Power Level Standard Unit
dB(A)
95
95
96
96
Sound Power Level Standard Unit + Option 15
dB(A)
93
93
94
94
Seasonal
ESEER
COOLING
Efficiency*
Full load performances*
C1
Nominal capacity
kW
561.2
631.3
670.2
721.4
C1
EER
kW/kW
2.43
2.45
2.44
2.42
C1
Eurovent Energy Class
E
E
E
E
kW/kW
4.06
4.06
4.08
4.00
Sound Power Level Standard Unit + Options 15LS
dB(A)
89
89
89
90
Operating weight - standard unit†
kg
4627
4873
5362
5609
Seasonal Efficiency*
ESEER
Compressors
Hermetic scroll, 48.3 r/s
Refrigerant
R-410A
Capacity control
Pro-Dialog Plus
Condensers
All aluminium micro-channel heat exchanger (MCHE)
Fans
Axial Flying Bird 4 with rotating shroud
Quantity
Total air flow (high speed)
l/s
Evaporator
9
10
11
12
40623
45139
49653
54167
HEATING HEATING
Unit with Option 15LS
Direct expansion, shell-and-tube
Dimensions
Length
mm
5992
7186
Depth
mm
2253
2253
Height
mm
2297
2297
AIR TREATMENT
C1 Cooling mode conditions: Water heat exchanger, entering/leaving temperature 12°C/7°C, fouling factor 0 m2 K/W. Outside air temperature 35°C
*
In accordance with standard EN14511-3:2013
† Weight shown is a guideline only.
Eurovent certified data
Option 15 = compressor enclosure
Option 15LS = low sound option
For 30RB 162-262 units with option 280 (shell-an d-tube heat exchanger) please refer to the specific product literature
Electrical data
30RB (without hydronic module)
602
672
732
802
Power circuit
Nominal power supply
V-ph-Hz
Control circuit supply
400-3-50 ± 10%
kW
191/96
191/127
255/96
255/127
Nom. current draw** - circuits A + B/C
A
251/125
251/167
334/125
334/167
Max. start-up current*** - circuits A + B/C
A
535/371
535/426
645/371
645/426
*
**
***
Power input, compressors and fans, at the unit operating limits (saturated suction temperature 10°C, saturated condensing temperature 65°C) and nominal voltage of 400 V (data given
on the unit nameplate).
Nom. unit current draw at standardised Eurovent conditions: evaporator entering/leaving water temperature 12°C/7°C, outside air temperature 35°C.
Maximum instantaneous start-up current at operating limit values (maximum operating current of the smallest compressor(s) + fan current + locked rotor current of the largest compressor).
Note: Units 30RB 602-802 have two electrical connection points.