AHI Carrier Catalog | Page 134

COOLING

Options

Options No . Description Advantages
Low noise level
15
Aesthetic and sound absorbing compressor enclosure
Noise level reduction by 1 to 2 dB ( A )
Very low noise level
Aesthetic and sound absorbing compressor
15LS enclosure associated with low-speed fans
Noise level reduction by 6 to 7 dB ( A )
High ambient temperature
16
Unit equipped with electrical panel cooling fan
Extended unit part-load operation up to 52 ° C ambient temperature
IP54 control boxes
20A
Unit with IP54 control box ( standard feature ) and compressor enclosure
Increased leak tightness of control boxes against intrusion of dusts and water .
Grilles and enclosure
23 panels
Metal grilles on the 4 unit sides , plus side enclosure panels at each end of the coil
Improves aesthetics , protection against intrusion to the unit interior , coil and piping protection against impacts .
Enclosure panels
23A
Side enclosure panels at each end of the coil
Improves aesthetics , coil and piping protection against impacts .
Soft Starter
25
Electronic starter on each compressor
Reduced start-up current
Winter operation down to -20 ° C
28
Fan speed control of lead fan for each circuit using a variable frequency drive
Stable unit operation for outside air temperature from 0 ° C down to -20 ° C
Winter operation down to -10 ° C
28B
Dual-speed lead fan for each circuit
Stable unit operation for outside air temperature from 0 ° C down to -10 ° C
Winter operation down to -10 ° C low speed
28C
Low speed fans and dual low speed lead fan on each circuit
Reduces the noise level and enables stable unit operation for outside air temperature down to -10
° C
Evaporator frost protection
41
Electric heater on the evaporator
Evaporator and hydronic module frost
42A protection
Electric heater on the evaporator , hydronic module and optional expansion tank
Partial heat recovery
49
Unit equipped with one desuperheater on each refrigerant circuit
Total heat recovery
50
Unit equipped with additional heat exchanger in parallel with the condenser coils .
Unit equipped with supplementary water outlet
Master / slave operation
58
temperature sensor kit to be field-installed allowing master / slave operation of two units connected in
parallel
Compressor suction and discharge valves 92A
Compressor discharge valves
HP single-pump hydronic module
HP dual-pump hydronic module
LP single-pump hydronic module
LP dual-pump hydronic module
93A
116R
116S
116T
116U
HP variable-speed single-pump hydronic 116V mod .
HP variable-speed dual-pump hydronic mod .
Dx Free Cooling system on two circuits
Dx Free Cooling system on one circuit 118B
CCN to J-Bus
148B gateway CCN to Lon gateway 148D
Bacnet / IP gateway 149
Energy Management Module
Touch Pilot control
Power factor correction
Shut-off valves on the compressor suction and discharge piping
Shut-off valves on the compressor discharge piping
Single high-pressure water pump , water filter , electronic water flow control , pressure transducers . See hydronic module option chapter Dual high-pressure water pump , water filter , electronic water flow control , pressure transducers . See hydronic module option chapter Single low-pressure water pump , water filter , electronic water flow control , pressure transducers . See hydronic module option chapter Dual low-pressure water pump , water filter , electronic water flow control , pressure transducers . See hydronic module option chapter Single high-pressure water pump with variable speed drive ( VSD ), water filter , electronic water flow control , pressure transducers . Multiple possibilities of water flow control . See hydronic module option chapter . Dual high-pressure water pump with variable speed drive ( VSD ), water filter , electronic flow switch ,
116W pressure transducers . Multiple possibilities of water flow control . See hydronic module option chapter . Patented Carrier free-cooling system with cooling micro-pump on both refrigerant circuits . Operation
118A without glycol , no extra free-cooling coil . See Dx Free-cooling option chapter . Patented Carrier free-cooling system with cooling micro-pump on one refrigerant circuit . Operation without glycol , no extra free-cooling coil . See Dx Free-cooling option chapter .
156
158A
231
Two-directional communication board complying with JBus protocol Two-directional communication board complying with Lon Talk protocol
Two-directional high-speed communication using BACnet protocol over Ethernet network ( IP )
Control board with additional inputs / outputs . See Energy Management Module option chapter .
Touch Pilot control supplied with a 7 inch colour touch screen user interface
Capacitors for automatic regulation of power factor ( cos phi ) value to 0.95
Evaporator module frost protection between 0 ° C and -20 ° C outside air temperature
Evaporator and hydronic module frost protection between 0 ° C and -20 ° C outside air temperature
Production of free high-temperature hot-water simultaneously with chilled water production Production of free hot-water simultaneously with chilled water production
Optimised operation of two chillers connected in parallel with operating time equalisation
Use 30RBM / 30RBP
30RBM / 30RBP 160-520 30RBM / 30RBP 160-520
30RBM 160-520
30RBM 160-520
30RBM / 30RBP 160-520
30RBM / 30RBP 160-520
30RBM / 30RBP 160-520
30RBM 160-520
30RBM 160-520
30RBM 160-520
30RBM / 30RBP 160-520
30RBM / 30RBP 160-520
30RBM / 30RBP 160-520 30RBM / 30RBP 160-520
30RBM / 30RBP 160-520
Simple maintenance . Possibility to store the 30RBM / 30RBP refrigerant charge in the cooler or condenser side 160-520 during servicing . Simple maintenance . Possibility to store the refrigerant charge in the condenser side during servicing .
Easy and fast installation ( plug & play )
Easy and fast installation ( plug & play )
Easy and fast installation ( plug & play )
Easy and fast installation ( plug & play )
Easy and fast installation ( plug & play ), significant pumping energy cost savings ( more than twothirds ), tighter water flow control , improved system reliability Easy and fast installation ( plug & play ), significant pumping energy cost savings ( more than twothirds ), tighter water flow control , improved system reliability
Energy savings for applications with cooling demand throughout the entire year
Energy savings for applications with reduced demand for cooling in the cold season ( e . g . office space with computer room , meeting rooms , etc .)
Connects the unit by communication bus to a building management system Connects the unit by communication bus to a building management system Easy and high-speed connection by ethernet line to a building management system . Allows access to multiple unit parameters .
30RBM / 30RBP 160-520
30RBM / 30RBP 160-520
30RBM / 30RBP 160-520
30RBM / 30RBP 160-520
30RBM / 30RBP 160-520
30RBM / 30RBP 160-520
30RBM / 30RBP 160-520
30RBM / 30RBP 160-520
30RBM / 30RBP 160-520
30RBM / 30RBP 160-520 30RBM / 30RBP 160-520
30RBM / 30RBP 160-520
Extended remote control capabilities ( oet-point 30RBM / 30RBP reset , ice storage end , demand limits , boiler on / off 160-520 command , etc .) Control with advanced communication technology
30RBM / 30RBP over Ethernet ( IP ), user-friendly and intuitive user
160-520 interface with 7 " colour touch screen Reduction of the real electrical power , compliance with minimum power factor limit set by utilities
30RBM / 30RBP 160-520
134 C A R R I E R 2 0 1 6 / 2 0 1 7