AHI Carrier Catalog | Page 131
AIR-COOLED SCROLL CHILLERS WITH
GREENSPEED INTELLIGENCE 30RBM/30RBP 160-520
®
Physical data
30RBP
160
180
200
220
260
300
330
360
400
430
470
520
Cooling
Nominal cooling capacity
kW
168
180
197
216
261
300
331
365
397
430
464
523
ESEER
kW/kW
4.18
4.21
4.14
4.18
4.15
4.37
4.28
4.37
4.26
4.36
4.44
4.30
EER
kW/kW
Eurovent class cooling
3.04
3.12
2.98
2.97
2.90
2.97
2.92
2.95
2.90
2.94
2.90
2.90
B
A
B
B
B
B
B
B
B
B
B
B
Air conditioning application††- standard unit
Nominal cooling capacity
kW
168
181
198
216
262
301
331
366
398
431
465
524
ESEER
kW/kW
4.31
4.36
4.29
4.37
4.32
4.53
4.41
4.53
4.39
4.50
4.60
4.48
EER
kW/kW
3.07
3.16
3.03
3.01
2.93
3.00
2.94
2.98
2.93
2.97
2.93
2.93
IPLV
kW/kW
4.76
4.85
4.73
4.85
4.75
5.00
4.83
5.00
4.81
4.92
5.00
4.84
Sound power level***
dB(A)
91
92
92
92
92
93
93
93
93
94
94
94
Sound pressure level at 10 m****
dB(A)
59
60
60
60
60
60
60
61
61
62
62
62
COOLING
Air conditioning application as per EN14511-3:2013† - standard unit
Sound levels
Standard unit
dB(A)
89
90
90
90
90
91
91
92
92
93
93
93
dB(A)
57
58
58
58
58
59
59
60
60
61
61
61
Standard unit + option 15LS*
Sound power level***
dB(A)
85
85
85
86
86
86
86
87
87
88
88
88
Sound pressure level at 10 m****
dB(A)
53
53
53
54
54
54
54
55
55
55
55
56
mm
2410
Dimensions - standard unit
Length
3604
4797
Width
mm
2253
2253
2253
Height
mm
2297
2297
2297
Operating Weight **
Standard unit
kg
1252
1293
1293
1423
1445
1901
1937
2105
2162
2603
2621
2827
Standard unit + option 15*
kg
1334
1376
1376
1531
1553
2027
2063
2249
2306
2765
2783
3007
Standard unit + option 15 + option
116S*
kg
1473
1515
1516
1670
1707
2187
2267
2452
2509
3007
3024
3287
2
2
2
2
3
3
3
3
4
Compressors
Hermetic scroll 48.3 tr/s
Circuit A
1
1
1
Circuit B
2
2
2
2
2
3
3
3
3
4
4
4
No. of control stages
3
3
3
4
4
5
5
6
6
7
7
8
Refrigerant** - Standard unit
R410A
26.75
Circuit A
Circuit B
kg
8.40
10.90
10.90
12.60
13.10
14.70
15.40
20.30
21.10
23.50
23.50
teqCO2
17.5
22.8
22.8
26.3
27.4
30.7
32.2
42.4
44.1
49.1
49.1
55.9
kg
12.25
12.60
12.60
12.70
13.10
20.20
20.20
20.40
22.20
26.70
26.80
26.95
teqCO2
25.6
26.3
26.3
26.5
27.4
42.2
42.2
42.6
46.4
55.7
56.0
56.3
25
25
20
20
17
17
14
14
13
Capacity control
Pro-Dialog+ Control
Minimum capacity
%
33
Condensers
33
33
Eurovent certified data
A
R
R
I
E
R
2
0
1
6
/
2
0
1
7
131
CONTROLS
All-aluminium micro-channel heat exchanger (MCHE)
†
Eurovent-certified performances in accordance with standard EN14511-3:2013.
Cooling mode conditions: Evaporator water entering/leaving temperature 12 °C/7 °C, outside air temperature 35 °C. Evaporator fouling factor 0.00 m2. k/W
†† Gross performances, not in accordance with EN14511-3:2013. These performances do not take into account the correction for the proportional heating capacity and power input
generated by the water pump to overcome the internal pressure drop in the heat exchanger. Evaporator water entering/leaving temperature 12 °C/7 °C, outside air temperature 35 °C.
evaporator fouling factor 0.00 m2. k/W
* Options: 15 = Low noise level, 15LS = Very low noise level, 116S = High Pressure dual-pump hydronic module
** Weights are guidelines only. Refer to the unit nameplate.
*** In dB ref=10-12 W, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3 dB(A)). Measured in accordance with
ISO 9614-1 and certified by Eurovent.
**** In dB ref 20 µPa, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3 dB(A)). For information, calculated from
the sound power level Lw(A).
C
AIR TREATMENT
Sound power level***
Sound pressure level at 10 m****
HEATING HEATING
Standard unit + option 15*