AIR-COOLED SCROLL CHILLERS WITH
GREENSPEED INTELLIGENCE 30RBM/30RBP 160-520
®
-- Brazed plate heat exchangers with reduced water
pressure drops
-- Auto-adaptive microprocessor control with
Greenspeed® intelligence
-- Touch Pilot control with web connectivity possibilities
and colour touch screen user display
-- Extra energy savings through multiple options: Directexpansion free cooling system on one or two circuits,
hydronic free-cooling system, partial or total heat
recovery.
For operation in the most stringent environments that
cumulates high temperature, dusts and sand, the AquaSnap
(30RBM) can be equipped with optional IP54 electrical
box and cabinet fan to operate up to 52 °C outside air
temperature.
Both AquaSnap versions can be equipped with an integrated
hydronic module, limiting the installation to straight-forward
operations like connection of the power supply and the
Physical data
30RBM
160
180
200
220
260
300
330
360
400
430
470
520
216
261
300
331
365
397
430
464
523
COOLING
chilled water supply and return piping (plug & play), within the
dimensions of the standard unit.
Recommended by Carrier, the AquaSnap can be equipped
with one or two Greenspeed® variable-speed pumps to
save significant pumping energy cost (more than two-thirds),
ensure tighter water flow control, and improved overall
system reliability.
Cooling
Nominal cooling capacity
kW
168
181
198
ESEER
kW/kW
4.00
4.07
4.01
4.00
4.00
4.07
4.08
4.10
4.05
4.07
4.04
4.03
EER
kW/kW
3.04
3.12
2.98
2.97
2.90
2.97
2.92
2.95
2.90
2.94
2.90
2.90
B
A
B
B
B
B
B
B
B
B
B
B
Eurovent class cooling
Air conditioning application††- standard unit
Nominal cooling capacity
kW
168
182
199
216
262
301
331
366
398
431
465
524
ESEER
kW/kW
4.12
4.20
4.16
4.17
4.16
4.20
4.19
4.24
4.17
4.19
4.17
4.17
EER
kW/kW
3.07
3.16
3.02
3.01
2.93
3.00
2.94
2.98
2.93
2.97
2.93
2.93
IPLV
kW/kW
4.57
4.57
4.54
4.51
4.50
4.61
4.61
4.69
4.58
4.62
4.55
4.58
Sound levels
Standard unit
Sound power level***
dB(A)
91
92
92
92
92
93
93
93
93
94
94
94
Sound pressure level at 10 m****
dB(A)
59
60
60
60
60
60
60
61
61
62
62
62
HEATING HEATING
Air conditioning application as per EN14511-3:2013† - standard unit
dB(A)
89
90
90
90
90
91
91
92
92
93
93
93
dB(A)
57
58
58
58
58
59
59
60
60
61
61
61
Standard unit + option 15LS*
Sound power level***
dB(A)
85
85
85
86
86
86
86
87
87
88
88
88
Sound pressure level at 10 m****
dB(A)
53
53
53
54
54
54
54
55
55
55
55
56
Length
mm
2410
3604
4797
Width
mm
2253
2253
2253
Height
mm
2297
2297
2297
Dimensions - standard unit
Operating Weight **
Standard unit
kg
1216
1257
1257
1387
1408
1865
1901
2069
2125
2545
2563
2761
Standard unit + option 15*
kg
1299
1339
1340
1495
1516
1991
2027
2212
2269
2707
2726
2941
Standard unit + option 15 +
option 116S*
kg
1438
1479
1479
1634
1670
2151
2231
2416
2472
2950
2967
3221
†
Eurovent-certified performances in accordance with standard EN14511-3:2013.
Cooling mode conditions: Evaporator water entering/leaving temperature 12 °C/7 °C, outside air temperature 35 °C. Evaporator fouling factor 0.00 m2. k/W
†† Gross performances, not in accordance with EN14511-3:2013. These performances do not take into account the correction for the proportional heating capacity and power input generated
by the water pump to overcome the internal pressure drop in the heat exchanger. Evaporator water entering/leaving temperature 12 °C/7 °C, outside air temperature 35 °C. evaporator fouling
factor 0.00 m2. k/W
* Options: 15 = Low noise level, 15LS = Very low noise level, 116S = High Pressure dual-pump hydronic module
** Weights are guidelines only. Refer to the unit nameplate.
*** In dB ref=10-12 W, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3 dB(A)). Measured in accordance with
ISO 9614-1 and certified by Eurovent.
**** In dB ref 20 µPa, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3 dB(A)). For information, calculated from
the sound power level Lw(A).
Eurovent certified data
C
A
R
R
I
E
R
2
0
1
6
/
2
0
1
7
129
CONTROLS
Sound power level***
Sound pressure level at 10 m****
AIR TREATMENT
Standard unit + option 15*